Microbiologically Influenced Corrosion in Hydronic Heating Systems

机译:循环加热系统中受微生物影响的腐蚀

获取原文
获取原文并翻译 | 示例
           

摘要

Open-laop hydronic heating systems have been found to provide a breeding ground for bacteria, including bacteria associated with microbiologically influenced corrosion (MIC). Microbiologically influenced corrosion of brass fittings, which may contain up to 8% lead in potable water applications, has been linked to high copper and lead levels in water samples taken from the hydronic-loop tubing. The contamination is likely concentrated in slime deposits found within the tubing. These slime deposits can enter the potable water supply, resulting in potential copper and lead exposure levels considerably above Environmental Protection Agency (EPA) guidelines. The authors recommend that hydronic heating systems incorporate a closed-loop design to prevent personal exposure and to provide for use of corrosion-inhibiting additives.
机译:已经发现开放式循环水加热系统为细菌,包括与微生物影响的腐蚀(MIC)相关的细菌提供了温床。微生物对黄铜配件的腐蚀影响,在饮用水应用中可能含有多达8%的铅,这与从循环回路管道中抽取的水样中的铜和铅含量高有关。污染物可能集中在管道内发现的粘泥沉积物中。这些沉积物会进入饮用水,导致潜在的铜和铅暴露水平大大超过美国环境保护署(EPA)的规定。作者建议,水力加热系统应采用闭环设计,以防止个人接触并提供防腐蚀添加剂。