首页> 外文期刊>Wind Engineering >Simulated Onshore-Fault Ride Through of Offshore Wind Farms Connected Through VSC HVDC
【24h】

Simulated Onshore-Fault Ride Through of Offshore Wind Farms Connected Through VSC HVDC

机译:通过VSC HVDC连接的海上风电场的陆上故障穿越模拟

获取原文
获取原文并翻译 | 示例
       

摘要

Effective Onshore-Fault Ride Through was demonstrated by simulation for a Fixed Speed Induction Generator (FSIG) offshore wind farm connected through a Voltage Source Converter HVDC link. When a terrestrial grid fault occurs, power through the onshore converter reduces and the DC link voltage increases. A control system was then used to block the offshore converter. The offshore AC network voltage was reduced to achieve rapid power rejection. Reactive power at the onshore converter was controlled to support the AC network voltage according to the GB Grid Code requirements. Two cases, a 200 ms terrestrial fault and a 50% retained voltage fault of duration 710 ms, at the grid connection point were studied. The simulation results show that power blocking at the offshore converter was effective and the DC link voltage was controlled.
机译:通过电压源转换器HVDC链路连接的固定速度感应发电机(FSIG)海上风电场的仿真,证明了有效的陆上故障穿越能力。发生地面电网故障时,通过岸上转换器的功率会降低,直流母线电压也会升高。然后,使用控制系统来封锁海上转炉。降低海上交流网络电压以实现快速功率抑制。根据GB电网规范的要求,对岸上转换器的无功功率进行了控制,以支持AC网络电压。研究了两种情况,即在电网连接点发生的200 ms地面故障和持续时间为710 ms的50%保留电压故障。仿真结果表明,离岸变流器的功率闭锁是有效的,并且控制了直流母线电压。