In this study, performance assessment of an integrated cooling plant having both free cooling system and solar powered single-effect lithium bromide-water absorption chiller in operation since August 2002 in Oberhausen, Germany, was performed. A floor space of 270 m~2 is air-conditioned by the plant. The plant includes 35.17 kW cooling (10-RT) absorption chiller, vacuum tube collectors' aperture area of 108 m~2, hot water storage capacity of 6.8 m~3, cold water storage capacity of 1.5 m~3 and a 134 kW cooling tower. The results show that free cooling in some cooling months can be up to 70% while it is about 25% during the 5 years period of the plant operation. For sunny clear sky days with equal incident solar radiation, the daily solar heat fraction ranged from 0.33 to 0.41, collectors' field efficiency ranged from 0.352 to 0.492 and chiller COP varies from 0.37 to 0.81, respectively. The monthly average value of solar heat fraction varies from 31.1% up to 100% and the five years average value of about 60%. The monthly average collectors' field efficiency value varies from 34.1%) up 41.8% and the five-year average value amounts about 28.3%. Based on the obtained results, the specific collector area is 4.23 (m~2/kW_(cold)) and the solar energy system support of the institute heating system for the duration from August 2002 to November 2007 is 8124 kWh.
机译:在这项研究中,对自2002年8月以来在德国奥伯豪森运行的具有自然冷却系统和太阳能单效溴化锂-吸水式冷却器的综合冷却装置的性能进行了评估。该工厂对270 m〜2的建筑面积进行了空调。该工厂包括35.17 kW冷却(10-RT)吸收式制冷机,真空管集热器的开口面积为108 m〜2,热水存储容量为6.8 m〜3,冷水存储容量为1.5 m〜3和134 kW冷却塔。结果表明,在某些冷却月份中,自然冷却最多可达到70%,而在工厂运营的5年中大约为25%。对于具有相等入射太阳辐射的晴朗晴朗天,日太阳热量比例在0.33到0.41之间,集热器的场效率在0.352到0.492之间,冷水机组COP在0.37到0.81之间。太阳热分数的月平均值从31.1%到100%不等,五年平均值约为60%。每月平均收集者的现场效率值从34.1%上升到41.8%,五年平均值约为28.3%。根据获得的结果,特定的集热器面积为4.23(m〜2 / kW_(冷)),研究所供热系统从2002年8月至2007年11月的太阳能系统支持为8124 kWh。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号