Determination of Energy Saving of Cool Roof on an Office Building in Hyderabad, India Using Calibrated Simulation

机译:使用校准模拟确定印度海得拉巴一栋办公楼的凉爽屋顶节能

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The method of calibrated simulation has been used to estimate the energy savings by application of cool roof for the building of Satyam Learning Centre (SLC) at Hyderabad (India). Energy simulation model of the building was created using 'DesignBuilder v.1.95' and the building was monitored for few months. Mismatch between the simulation results and actual energy consumption has been reduced to obtain the calibrated model of the building using the method suggested in IPMVP Option-D. The calibrated model is then used to predict energy saving from the cool roof; the annual cooling energy savings were 19.4 kWMn~2. This saving corresponds to 9% reduction in annual air conditioning load and 5% reduction in overall annual energy consumption. Cost/benefit analysis for cool roof at SLC showed a 2.4 year financial payback period.
机译:校准模拟的方法已用于通过在印度海得拉巴的萨蒂扬学习中心(SLC)建造凉爽屋顶来估算节能量。使用“ DesignBuilder v.1.95”创建了建筑物的能源模拟模型,并对建筑物进行了几个月的监视。使用IPMVP Option-D中建议的方法,可以减少模拟结果与实际能耗之间的不匹配,从而获得建筑物的校准模型。然后,使用校准后的模型来预测凉爽屋顶的节能量。每年节省的冷却能源为19.4 kWMn〜2。节省的费用相当于每年减少9%的空调负荷,减少5%的整体年度能耗。 SLC凉爽屋顶的成本/收益分析显示2.4年的财务回收期。