首页> 外文期刊>IEEE sensors journal >Real-Time Wireless, Contactless, and Coreless Monitoring of the Current Distribution in Substation Conductors for Fault Diagnosis
【24h】

Real-Time Wireless, Contactless, and Coreless Monitoring of the Current Distribution in Substation Conductors for Fault Diagnosis

机译:实时无线,无接触和无芯监控变电站导体中电流分布,以进行故障诊断

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Parallel conductors are found in electrical transmission and distribution systems including large ampacity feeders or loads. However, current unbalance often occurs, especially in alternating current systems. This non-regular current distribution causes overheating and premature aging, facilitating the occurrence of failures. Therefore, a fault diagnosis system is a must, which can be performed by monitoring in real time the individual currents flowing through the conductors. In this paper, a setup, including three parallel aluminum conductors of large cross-section, a spacer, and two terminal substation connectors, is analyzed. A real-time, wireless, coreless, and contactless system based on three low-cost Hall effect sensors is proposed, which is also easy to install. The experimental results, which include 14 cases comprising 13 fault modes and a well-installed set, prove the suitability and potential of the proposed approach since it allows a correct real-time detection of all analyzed faulty conditions as well as the detection of currents exceeding the thermal rating of the conductors.
机译:在包括大型载流量馈线或负载的输配电系统中发现了并联导体。但是,电流不平衡经常发生,特别是在交流系统中。这种不规则的电流分布会导致过热和过早老化,从而促进故障的发生。因此,必须有一个故障诊断系统,该系统可以通过实时监控流过导体的各个电流来执行。在本文中,分析了一种设置,包括三个大横截面的平行铝导体,一个垫片和两个变电站终端连接器。提出了一种基于三个低成本霍尔效应传感器的实时,无线,无核,非接触式系统,该系统也易于安装。实验结果包括14种情况,包括13种故障模式和一套完善的安装,证明了该方法的适用性和潜力,因为它可以对所有分析出的故障情况进行正确的实时检测,并且可以检测出超过导体的热额定值。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号