首页> 外文期刊>Science, Measurement & Technology, IET >Statistical correlation technique for transient signal analysis during impulse testing of transformers
【24h】

Statistical correlation technique for transient signal analysis during impulse testing of transformers

机译:变压器脉冲试验期间瞬态信号分析的统计相关技术

获取原文
获取原文并翻译 | 示例
           

摘要

The reliable technique for identification of winding insulation faults in a transformer is necessary for a testing engineer during impulse test. In this study, a statistical correlation technique is proposed to estimate the 'best correlation' between transient signals for passed (withstood the impulse voltage) or failed (not withstood) conditions of the insulations. In this study, normalised reduced impulse voltage is considered initially as a reference signal. The next successive impulse test sequences due to rated test voltage are correlated as a test signal with a reference signal using a proposed technique. It makes a 'good correlation value along with its directions' between the reference signal and test signal based on measured the applied impulse voltage waveshape and its winding response. The fundamentals of the correlation coefficient, curve fitting techniques, conditional variance, normalisation and time delay index are integrated effectively to predict the characteristics (degree/magnitude and direction) of correlation between the signals. 2.5-MVA 11/0.433 kV (distribution transformer), 0.3-MVA 34.5/0.415 kV (earthing transformer) and 250-MVA 500/275/33 kV (power transformer) are effectively utilised to validate proposed technique. The advantage of the proposed technique is validated with partial discharge detection in windings due to an impulse voltage application using an 11 kV single-layer winding.
机译:用于识别变压器中的卷绕绝缘故障的可靠技术对于脉冲测试期间的测试工程是必要的。在该研究中,提出了一种统计相关技术来估计通过(脉冲电压的脉冲电压)或失败(不带ood)条件的瞬态信号之间的“最佳相关性”。在该研究中,最初认为归一化的减小的脉冲电压作为参考信号。由于额定试验电压引起的下一个连续脉冲测试序列与使用所提出的技术的参考信号相关的测试信号。基于测量的脉冲电压波沿及其绕组响应,它在参考信号和测试信号之间具有“良好的相关值”以及其方向“。相关系数,曲线拟合技术,条件方差,归一化和时间延迟指数的基础是有效地集成的,以预测信号之间的相关性的特性(度/幅度和方向)。 2.5-MVA 11 / 0.433 kV(配电变压器),0.3-mVA 34.5 / 0.415 kV(接地变压器)和250-MVA 500/275/33 kV(电力变压器)可有效地利用,以验证提出的技术。由于使用11kV单层绕组脉冲电压施加,所提出的技术的优点是横跨绕组的横档检测。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号