Double-conversion UPS systems, as shown in Figure 1, are composed by 4 conversion stages: (ⅰ) rectifier stage to convert AC power from the grid to DC power, (ⅱ) inverter stage to convert DC power to AC power for the load, (ⅲ) DC/DC converter for the battery to convert DC power to DC power and (ⅳ) DC-link balancer circuit to convert dc power to dc power. For a modular UPS system, the reliability is high since each UPS module is independent to the other UPS modules. The DC rails are therefore on purpose not connected together, in order to avoid the loss of all UPS modules in case of a DC short-circuit (e.g., failure of one electrolytic capacitor).
机译:如图1所示,双转换UPS系统由4个转换级组成:(ⅰ)整流器级,将来自电网的交流电转换为直流电;(ⅱ)逆变器级,将负载的直流电转换为交流电,(ⅲ)电池的DC / DC转换器将DC电源转换为DC电源,(ⅳ)DC-link平衡器电路将DC电源转换为DC电源。对于模块化UPS系统,可靠性很高,因为每个UPS模块都独立于其他UPS模块。因此,直流母线故意不连接在一起,以避免在直流短路(例如,一个电解电容器发生故障)的情况下丢失所有UPS模块。