摘要

Regulation No. 507 in The Institution's Regulations for the Electrical Equipment of Buildings calls for a measurement of the earth-loop impedance and gives a method by which this can be done. Several instruments have been devised and are available to carry out this test, but all draw their testing current from the mains and are thus liable to serious errors. Records taken with a recording voltmeter show that in most cases there is already a voltage drop in the neutral conductor, which is varying continuously and rapidly. It is shown both theoretically and by practical tests that instruments of this character can have errors under these conditions amounting to 100% or more. Any instrument intended to carry out these tests must be such that it will give the correct value despite the presence of the continuously varying voltage drop in the neutral. An instrument is described which draws its testing current from its own hand-driven generator and is free from these errors. The Regulation also calls for a measurement of impedance, but it is suggested that in most cases the difference between impedance and resistance of an earth loop is so small that an instrument measuring resistance will be sufficient.
机译:《建筑物电气设备法规》中第507号法规要求测量接地回路阻抗,并提供了一种可以做到这一点的方法。已经设计了几种仪器并可以进行该测试,但是所有仪器均从电源中汲取测试电流,因此容易造成严重错误。用记录电压表获得的记录表明,在大多数情况下,中性导体中已经存在电压降,该电压降连续且快速变化。从理论上和实际测试中都可以证明,在这种情况下,具有这种特性的仪器的误差可能达到100%或更高。任何打算进行这些测试的仪器都必须确保即使中性线中存在不断变化的压降,也能给出正确的值。描述了一种仪器,该仪器从其自己的手动发电机获取测试电流,并且没有这些误差。该法规还要求测量阻抗,但是建议在大多数情况下,接地回路的阻抗和电阻之间的差异非常小,以至于仪器测量电阻就足够了。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号