Protection of station equipment against lightning over-voltages is usually effected, by voltage-limiting devices such as spark-gaps or surge diverters. When there is appreciable separation between two items of equipment a protective device located near one may not be effective in limiting the voltage at the other to a safe value. The paper is in two parts: in Part 1 the factors determining the most suitable location for the device and its range of protection are investigated, and it is shown that, except for terminal stations involving only one overhead line, the most effective position as on the equipment nearest the overhead line. It is also shown that the range of protection which determines whether more than one protective device is desirable is very dependent on the steepness of front of the over-voltage. The steepness is dependent on the attenuation due to corona during the passage of the over-voltage along the overhead line; this question is examined in Part 2.
机译:通常通过限压设备(例如火花隙或电涌分流器)来保护站设备免受雷电过电压的影响。当两套设备之间有明显的间隔时,位于其中一项附近的保护装置可能无法有效地将另一项上的电压限制在安全值内。本文分为两个部分:在第1部分中,研究了确定该设备最合适的位置及其保护范围的因素,结果表明,除了仅包含一条架空线的终端站以外,最有效的位置为最接近架空线的设备。还表明,确定是否需要一个以上保护装置的保护范围在很大程度上取决于过电压前部的陡度。陡度取决于过电压沿架空线通过时由于电晕而引起的衰减。该问题在第2部分中进行了讨论。