This two-part paper deals with the early detection of an impending voltage instability from the system states provided by synchronized phasor measurements. Recognizing that voltage instability detection requires assessing a multidimensional system, the method fits a set of algebraic equations to the sampled states, and performs an efficient sensitivity in order to identify when a combination of load powers has passed through a maximum. This second part of the paper presents simulation results obtained from detailed time-domain simulation of the Nordic32 test system, without and with measurement noise, respectively. Several practical improvements are described such as anticipation of overexcitation limiter activation, and use of a moving average filter. Robustness to load behavior, non-updated topology and unobservability is also shown. Finally a comparison with Thevenin impedance matching criterion is provided.
机译:这篇由两部分组成的论文涉及从相量测量提供的系统状态中早期检测即将发生的电压不稳定性。认识到电压不稳定性检测需要评估多维系统,因此该方法将一组代数方程式拟合到采样状态,并执行有效的灵敏度以识别负载功率的组合何时已通过最大值。本文的第二部分介绍了从Nordic32测试系统的详细时域仿真获得的仿真结果,分别没有测量噪声和有测量噪声。描述了一些实际的改进,例如预期过度励磁限制器激活以及使用移动平均滤波器。还显示了负载行为的鲁棒性,未更新的拓扑和不可观察性。最后,与戴维南阻抗匹配标准进行了比较。