首页> 外文期刊>IEEE Transactions on Power Systems >On Area Control Errors, Area Injection Errors, and Textbook Automatic Generation Control
【24h】

On Area Control Errors, Area Injection Errors, and Textbook Automatic Generation Control

机译:面积控制误差,区域注射误差和教科书自动生成控制

获取原文
获取原文并翻译 | 示例

摘要

We reexamine and critique the classical area control error concept used in automatic generation control, and propose a new error signal termed the area injection error. Unlike the ACE, the AIE uses direct measurement of generator power levels, yielding improved AGC performance in the presence of bias uncertainty and nonlinearity in generator turbine-governor responses. As a by-product of our analysis, we conclude that the effective frequency biasing found in a common textbook implementation of AGC is larger than intended, resulting in unintended interaction between control areas. Our theory is validated via simulations on a detailed two-area test system.
机译:我们重新审视和批判在自动生成控制中使用的经典控制错误概念,并提出了一个新的误差信号称为区域注入误差。与ACE不同,AIE使用直接测量发电机功率水平,在发电机涡轮调速器响应中存在偏差不确定度和非线性的存在下产生改善的AGC性能。作为我们分析的副产物,我们得出的结论是,在AGC的常见教科书实施中发现的有效频率偏置大于预期,导致控制区域之间的意外互动。我们的理论通过对详细的两区域测试系统进行仿真进行验证。