Wide-area control helps damp the inter-area oscillations in modern power systems. However, compared to traditional local control, it is more vulnerable to cyber attacks due to its dependence on remote real-time-communicated measurements. In this paper, a formal mathematical framework for analyzing resilience of various wide-area controllers under adversarial scenarios is proposed. A novel resilience index based on the H-2 norm of the post-attack closed-loop system is defined. Computation of such an index is, in general, challenging due to the combinatorial nature of the attack profiles and the bilinear nature of the problem. To address these difficulties, a gradient-based path-following-like solution is developed in this paper to solve a relaxed version of the original non-convex problem. Case studies on IEEE 39-bus system are performed to demonstrate the usage of the proposed framework.
机译:广域控制有助于抑制现代电力系统中的区域间振荡。但是,与传统的本地控制相比,由于它依赖于远程实时通信的测量值,因此更容易受到网络攻击。本文提出了一种正式的数学框架,用于分析对抗情况下各种广域控制器的弹性。定义了一种基于攻击后闭环系统的H-2范式的新型弹性指数。通常,由于攻击特征的组合性质和问题的双线性性质,计算这样的指数具有挑战性。为了解决这些困难,本文开发了一种基于梯度的路径跟踪类解决方案,以解决原始非凸问题的宽松版本。对IEEE 39总线系统进行了案例研究,以证明所提出框架的用法。