Variable, nonlinear tie-line frequency bias for interconnected systems control

机译:可变的非线性联络线频率偏置,用于互连系统控制

获取原文
获取原文并翻译 | 示例

摘要

In February 1984, Union Electric began implementation of a test to identify the improvement to electric system automatic generation and tie-line control that could be achieved by the application of variable nonlinear tie-line frequency bias. Variable, nonlinear tie-line frequency bias is a better simulation of electric system frequency response than fixed straight-line bias because it recognizes the variable nature of a system's reaction to frequency changes. Important components of this response are the deadband in turbine-generator governors, variations in the number of online generators, and variations in load. The test showed that when tie-line frequency bias is better matched to system response, the result will be improved area-control error performance and reduced generating unit regulation. In addition, interconnection reliability is enhanced due to the fact that variable, nonlinear tie-line frequency bias does not inhibit the full governor response during large frequency disturbances, thereby providing better interconnected systems frequency stabilization.
机译:1984年2月,Union Electric开始实施一项测试,以确定对电气系统自动发电和联络线控制的改进,这可以通过应用可变非线性联络线频率偏置来实现。可变的非线性联络线频率偏差比固定的直线偏差更好地模拟了电气系统的频率响应,因为它可以识别系统对频率变化的反应的可变性。该响应的重要组成部分是涡轮发电机调速器的死区,在线发电机数量的变化以及负载的变化。测试表明,当联络线频率偏差更好地与系统响应匹配时,结果将是改善区域控制误差性能并减少发电机组调节。此外,由于可变的非线性联络线频率偏置不会在较大的频率扰动期间抑制完整的调节器响应,因此增强了互连可靠性,从而提供了更好的互连系统频率稳定性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号