首页> 外文期刊>IEEE Transactions on Power Systems >Improved contingency measures for operation and planning applications
【24h】

Improved contingency measures for operation and planning applications

机译:改进了用于运营和计划应用的应急措施

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Three new contingency measures are proposed and tested based on a large power system peak load base case. The Type II contingency measure is zero for all noncritical contingencies, has no misclassification or false alarm problems, and ranks contingencies according to their largest thermal limit violation. It should be used when operating conditions are known exactly. The Type III contingency measure has very small or zero contingency measure for noncritical contingencies, has no perceptible misclassification or false alarm problems, and appears to rank contingencies by their worst thermal limit violation. The Type III contingency measure is very useful for selecting contingencies where the precise operating conditions are unknown. A Type IV contingency measure sets branch weights to zero on all branches that do not experience thermal overloads for a set of contingencies. The Type IV contingency measure is useful for selecting single contingencies that when taken in combination could produce critical multiple contingencies.
机译:基于大型电力系统峰值负载的基本情况,提出并测试了三种新的应急措施。对于所有非关键意外事件,类型II应急措施为零,没有错误分类或错误警报问题,并且根据最大违反热极限的方式对意外事件进行排名。当确切了解运行条件时,应使用该传感器。 III类应变措施对非紧急事件的应变措施非常小或为零,没有可察觉的错误分类或错误警报问题,并且似乎按其最严重的热极限违规对其进行排名。 III类应变措施对于选择精确操作条件未知的突发事件非常有用。 IV类应变措施将在一组突发事件中没有热过载的所有分支上的分支权重设置为零。 IV类应变措施对于选择单个意外事件很有用,当结合使用这些意外事件时,可能会产生关键的多个意外事件。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号