首页> 外文期刊>Power and Energy Systems, CSEE Journal of >Experimental analysis on influence of temperature and bolted torque to DC contact resistance of terminal connector in UHV valve hall
【24h】

Experimental analysis on influence of temperature and bolted torque to DC contact resistance of terminal connector in UHV valve hall

机译:UHV阀门端子连接器电压与螺栓扭矩对直流接触电阻的实验分析

获取原文
获取原文并翻译 | 示例
           

摘要

The overheating problems of terminal connectors severely threaten the operation of ultra-high voltage projects and cause enormous losses of economy, so a higher current-carrying reliability of the connectors has an important engineering significance with the development of transmission capacity. In this paper, a bivariate mathematical model of contact resistance as functions of temperature and tightening torque was deduced based on the large current temperature rise tests. To perform such analysis, four typical terminal connectors, namely: overlapping terminal of aluminum plates, overlapping terminal of copper plates, overlapping terminal of plates with clad layer and overlapping terminal of copper rod with aluminum clamp, were chosen for the experiments. The changing rules of DC resistance with different tightening torques and different currents were studied. Then the empirical formula of contact resistance was deduced. Finally, temperature calculations of different terminal connectors were realized to verify the effectiveness of the bivariate mathematical model.
机译:终端连接器的过热问题严重威胁到超高电压项目的运行并导致经济巨大损失,因此连接器的更高电流承载可靠性随着传输容量的发展而具有重要的工程意义。本文基于大电流温度升高试验,推出了作为温度和拧紧扭矩的函数的接触电阻的二变型数学模型。为了执行这种分析,四个典型的终端连接器,即:铝板的重叠端子,铜板的重叠端子,具有铝夹的带有层叠层和铜棒的重叠端子的板的重叠端子,用于实验。研究了不同拧紧扭矩和不同电流的直流电阻的变化规则。然后推导出接触电阻的经验配方。最后,实现了不同终端连接器的温度计算以验证二元数学模型的有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号