首页> 外文期刊>Power Electronics, IET >Submodule configuration of HVDC-DC autotransformer considering DC fault
【24h】

Submodule configuration of HVDC-DC autotransformer considering DC fault

机译:考虑直流故障的HVDC-DC自耦变压器子模块配置

获取原文
获取原文并翻译 | 示例
           

摘要

This paper studies the submodule configuration of modular multilevel converter (MMC) based non-isolated HVDC-DC autotransformer (HVDC-AT) with DC fault blocking capability, including two-terminal and multi-terminal topologies. The operation principle of the HVDC-AT is described. Considering the arm current differences, the total number of required semiconductors for the HVDC-AT is derived and is compared with the MMC based isolated front-to-front DC transformer. A full operation process for the multi-terminal HVDC-AT considering DC fault is then presented, including normal operation, fault isolation and continuous operation of healthy converters after fault. The submodule configuration and fault recovery of the multi-terminal HVDC-AT are validated by simulations using PSCAD/EMTDC.
机译:本文研究了基于模块化多电平转换器(MMC)的具有直流故障阻止功能的非隔离HVDC-DC自耦变压器(HVDC-AT)的子模块配置,包括两端和多端拓扑。描述了HVDC-AT的工作原理。考虑到臂电流差异,可以得出HVDC-AT所需的半导体总数,并将其与基于MMC的隔离式前后直流变压器进行比较。然后给出了考虑直流故障的多端子HVDC-AT的完整运行过程,包括正常运行,故障隔离以及故障后健康转换器的连续运行。多端子HVDC-AT的子模块配置和故障恢复通过使用PSCAD / EMTDC的仿真进行了验证。