首页> 外文期刊>IEEE Transactions on Power Delivery >Characteristics of GIS disconnector-induced short rise-time transients incident on externally connected power system components
【24h】

Characteristics of GIS disconnector-induced short rise-time transients incident on externally connected power system components

机译:GIS隔离开关引起的短暂上升时间瞬变的特性,这些瞬变发生在外部连接的电力系统组件上

获取原文
获取原文并翻译 | 示例
       

摘要

The authors provide an indication of the waveshape and magnitude of transients which emerge from the SF/sub 6/ GIS and propagate to externally connected apparatus. Capacitively graded bushings, overhead line connections, etc. tend to reduce the magnitude and cause a slight degradation in the rise-time. Computer simulations and measurements have shown that external apparatus connected to GIS can be subjected to waveforms with rise-times in the range of 10-20 ns and voltage rate-of-rise as high as 40 MV/ mu s. This is comparable to or in excess of the rate of rise during a chopped wave test.
机译:作者提供了从SF / sub 6 / GIS出现并传播到外部连接设备的瞬态波形和幅度的指示。电容渐变的衬套,架空线连接等往往会减小强度,并导致上升时间略有下降。计算机仿真和测量表明,连接到GIS的外部设备可能会受到波形影响,其上升时间在10-20 ns范围内,电压上升率高达40 MV /μs。这相当于或超过斩波测试期间的上升速率。