首页> 外文期刊>IEEE Transactions on Power Delivery >New method for measurement of the resistive leakage currents of metal-oxide surge arresters in service
【24h】

New method for measurement of the resistive leakage currents of metal-oxide surge arresters in service

机译:测量使用中的金属氧化物避雷器电阻泄漏电流的新方法

获取原文
获取原文并翻译 | 示例
           

摘要

Various methods of determining the condition of zinc oxide (ZnO) surge arresters by means of measuring their leakage current are discussed. A method that minimizes the influence of harmonics in the system voltage when performing a harmonic analysis of the arrester leakage current presented. The presence of harmonics in the voltage has presented a great problem to earlier methods based on harmonic analysis, since these harmonics may interfere with the harmonics generated by the nonlinear resistance of the arrester. The favorable effect of the method presented is achieved by introducing a field probe which allows a compensation for the harmonics in the voltage. The main advantage of the new method is the low sensitivity to harmonics in the system voltage.
机译:讨论了通过测量其漏电流来确定氧化锌(ZnO)避雷器状态的各种方法。一种在对所提供的避雷器泄漏电流进行谐波分析时,将系统电压中谐波影响最小化的方法。电压中谐波的存在对基于谐波分析的早期方法提出了很大的问题,因为这些谐波可能会干扰避雷器非线性电阻产生的谐波。所介绍的方法的有利效果是通过引入一个可以补偿电压中谐波的场探头实现的。新方法的主要优点是对系统电压谐波的敏感性低。