首页> 外文期刊>IEEE Transactions on Power Delivery >Lightning-induced voltages on multiconductor overhead lines
【24h】

Lightning-induced voltages on multiconductor overhead lines

机译:多导体架空线上的雷电感应电压

获取原文
获取原文并翻译 | 示例

摘要

The effects of other conductors in a multiconductor overhead line on the voltages induced on a conductor by a nearby lightning strike are analyzed on the basis of previous studies on long single-conductor overhead lines. It is shown that the presence of other conductors affects the induced voltage of a conductor, particularly for vertically configured lines; however, the amount is less than that originally predicted. Ground wires reduce the magnitude of the induced voltages, thus acting as partial shields. The amount that the ground wires reduce the induced voltages on the conductors is dependent on the position of the ground wires in relation to the ungrounded conductors.
机译:在先前对长单导体架空线的研究基础上,分析了多导体架空线中其他导体对附近雷击感应到的导体电压的影响。结果表明,其他导体的存在会影响导体的感应电压,特别是对于垂直配置的线路;但是,该数量少于最初的预测。接地线可减小感应电压的大小,从而充当部分屏蔽。接地线减少导体上的感应电压的量取决于接地线相对于未接地导体的位置。