首页> 外文期刊>IEEE Transactions on Power Delivery >Transient overvoltages on a three terminal DC transmission system due to monopolar ground faults
【24h】

Transient overvoltages on a three terminal DC transmission system due to monopolar ground faults

机译:单极性接地故障导致三端直流输电系统上的瞬态过电压

获取原文
获取原文并翻译 | 示例
           

摘要

Transient overvoltages were investigated using the Electromagnetic Transients Program (EMTP) for a three-terminal DC transmission system. Pole-to-ground faults on a DC line were studied to investigate overvoltages on the healthy pole and also on the electrode lines. The effect of providing a metallic neutral conductor in one section of the three-terminal system was also studied, as was the sensitivity of the results to DC filter configuration and to neutral bus capacitance. It was found that the peak overvoltages for the DC line, especially near the converter stations, are sensitive to the DC filter configuration. The overvoltages near the converter stations were also found to be affected by the neutral bus capacitance.
机译:使用电磁瞬变程序(EMTP)对三端子DC传输系统进行了瞬态过电压研究。研究了直流线路上的极对地故障,以研究健康极和电极线上的过电压。还研究了在三端子系统的一部分中提供金属中性导体的效果,以及结果对DC滤波器配置和中性母线电容的敏感性。发现直流线路的峰值过电压,特别是在换流站附近,对直流滤波器的配置很敏感。还发现换流站附近的过电压受中性母线电容的影响。