Analysis of a harmonic overvoltage due to transformer saturation following load shedding on Hydro-Quebec-NYPA 765 kV interconnection

机译:Hydro-Quebec-NYPA 765 kV互连上的切负荷后变压器饱和引起的谐波过电压分析

获取原文
获取原文并翻译 | 示例
           

摘要

An analysis is presented of the harmonic overvoltage recorded on the interconnection between Hydro-Quebec and the New York Power Authority (NYPA) in the Chateauguay area. The overvoltage was caused by transformer saturation, following tripping of the 765 kV transmission line linking both systems. EMTP (electromagnetic transient program) simulation yielded good agreement with field measurements and was valuable in reevaluating operating practices at the Chateauguay station.
机译:分析了魁北克水电公司与Chateauguay地区纽约电力局(NYPA)之间的互连所记录的谐波过电压。过电压是由连接两个系统的765 kV输电线路跳闸后的变压器饱和引起的。 EMTP(电磁暂态程序)仿真与现场测量结果吻合良好,对于重新评估Chateauguay站的运行实践具有重要意义。