摘要

Conversion of an existing double circuit three-phase 115 kV overhead transmission line to six-phase operation will provide a commercial demonstration of feasibility of high phase order power transmission. An important part of this demonstration is specification of the phase/voltage conversion transformers and requirements to permit single pole switching of the line in a practical manner at minimum cost. Results are presented of engineering studies which led to selection of two delta-wye three-phase transformers at each end, one of each pair with reversed polarity to obtain the 60 degrees shift between phases.
机译:将现有的双回路三相115 kV架空输电线路转换为六相运行将提供高阶有序电力传输可行性的商业演示。该演示的重要部分是相/电压转换变压器的规格以及以最小的成本以实际方式允许线路的单极开关的要求。介绍了工程研究的结果,这些结果导致在每个端部选择两个三角型三相变压器,每对中的一个极性相反,以获得相之间60度的偏移。