AC and lightning performance of fiberglass crossarms aged in 115 kV transmission line

机译:115 kV输电线路中老化的玻璃纤维横梁的交流电和雷电性能

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents the results of an investigation of the electrical performance of 115 kV transmission line fiberglass crossarms used by Mississippi Power and Light Company. A transmission line fiberglass crossarm removed from service and companion crossarms stored outdoors but not in service were examined. The evaluation of electrical performance was based on flashover voltage value at AC voltage and standard lightning impulse as well as under dry and wet conditions. The tests were performed in the Mississippi State University High Voltage Laboratory. The obtained flashover voltages show no large difference in electrical strength of fiberglass crossarms removed from service and those stored outdoors. The added critical flashover voltage by fiberglass crossarm to the porcelain suspension insulators is presented versus the length of the fiberglass crossarm for dry and wet conditions.
机译:本文介绍了密西西比电力和照明公司使用的115 kV输电线路玻璃纤维横梁的电气性能的调查结果。检查了从服务中移出的传输线玻璃纤维横梁和存储在室外但未在使用中的配套横梁。电气性能的评估基于交流电压和标准雷电冲击下以及在干燥和潮湿条件下的闪络电压值。测试是在密西西比州立大学高压实验室进行的。所获得的闪络电压显示,退役的玻璃纤维横臂和存放在户外的玻璃横臂的电气强度没有太大差异。给出了在干燥和潮湿条件下,玻璃纤维横臂对瓷悬架绝缘子增加的临界闪络电压与玻璃纤维横臂的长度的关系。