Loading capability of HVDC transformer bushings with restricted oil circulation for use in HVDC valve halls

机译:HVDC阀厅中使用的油循环受限的HVDC变压器套管的负载能力

获取原文
获取原文并翻译 | 示例
       

摘要

The loading capability of a 500 kV high-voltage DC (HVDC) transformer bushing is calculated with some unusual conditions: the internal oil circulation in the bushing is blocked at the flange level and the ambient air temperature is raised to 60 degrees C. The theoretical model was verified with a full-scale heat run test on a 7.8 m long bushing. A 220 m/sup 3/ insulated test chamber was required to enclose the test set-up.
机译:500 kV高压直流(HVDC)变压器套管的负载能力是在某些异常条件下计算得出的:套管中的内部油循环在法兰高度处受阻,环境空气温度升高至60摄氏度。理论上该模型在7.8 m长的衬套上进行了全面的热运行测试。需要一个220 m / sup 3 /绝缘测试室来封闭测试装置。