A method to test the transient performance of a sampled-data relay is given. A model of one measuring unit of a digital relay is created on a personal computer. The simulations are compared with laboratory results obtained by applying digitally generated waveforms to the actual relay. Computer modeling of the digital relay is done within the models version of the Transient Analysis of Control System (TACS) subsection of the ElectroMagnetics Transient Program (EMTP). The input filter, analog-to-digital converter, Fourier fundamental frequency detector, and the relay measuring principle of one digital microprocessor-based relay are modeled. An actual 115 kV 150 mile long transmission line is simulated using the EMTP.
机译:给出了一种测试采样数据继电器瞬态性能的方法。在个人计算机上创建了数字继电器的一个测量单元的模型。将模拟与通过将数字生成的波形应用于实际继电器而获得的实验室结果进行比较。数字继电器的计算机建模是在电动瞬态程序(EMTP)的控制系统瞬态分析(TACS)小节的模型版本中完成的。对输入滤波器,模数转换器,傅立叶基频检测器以及一个基于数字微处理器的继电器的继电器测量原理进行了建模。使用EMTP模拟了一条实际的115 kV 150英里长的传输线。