Partial discharge (PD) scaling relationships, based on a recently developed theory, that allow prediction of PD magnitude in equivalent defects in different insulators for gas switchgear are presented. To maintain high levels of reliability, PD acceptance criteria of 0.5 to 1.0 pC are proposed for 550 kV insulators to obtain a standard of severity equivalent to that in existence at 138 kV. To achieve this level of testing, a number of techniques, including ultrawideband measurements, are proposed to improve present PD detection technology by at least two orders of magnitude. Sensitivities of better than 0.01 pC at up to 400 kV were routinely achieved in a factory-like environment.
机译:提出了一种基于最近发展的理论的局部放电(PD)比例关系,该关系允许预测气体开关设备的不同绝缘子中等效缺陷中的PD大小。为了保持较高的可靠性,建议对550 kV绝缘子的PD接受标准为0.5至1.0 pC,以获得与138 kV时存在的严重性相当的标准。为了达到这一水平的测试,提出了包括超宽带测量在内的多种技术,以将当前的PD检测技术提高至少两个数量级。在类似工厂的环境中,通常可以在400 kV的电压下获得优于0.01 pC的灵敏度。