首页> 外文期刊>IEEE Transactions on Power Delivery >Influence of switching operations on the vacuum interrupter dielectric strength
【24h】

Influence of switching operations on the vacuum interrupter dielectric strength

机译:开关操作对真空灭弧室介电强度的影响

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

The influence of switching operations on dielectric strength of vacuum interrupters is described. Detailed experimental procedure and numerical processing of experimental results are presented. The breakdown voltage and emission current before and after switching operations were experimentally determined for closing without current/breaking without current, closing without current/breaking with rated current, and closing without current/breaking of rated short-circuit current. The interconnect gap was varied, and DC lightning impulse voltage (1.2/50 mu s) and AC 50 Hz voltages were applied. Three types of commercially available vacuum interrupter were tested, two with transverse and one with axial magnetic field and all having CuCr contacts. It was found which physical mechanisms determine the influence of switching operations.
机译:描述了开关操作对真空灭弧室介电强度的影响。介绍了详细的实验程序和实验结果的数值处理。实验确定了开关操作前后的击穿电压和发射电流,以无电流时闭合/无电流时断开,无电流时闭合/用额定电流时断开,无电流时闭合/额定短路电流时断开。改变互连间隙,并施加直流雷电冲击电压(1.2 / 50μs)和交流50 Hz电压。测试了三种类型的市售真空灭弧室,其中两种具有横向磁场,一种具有轴向磁场,并且全部具有CuCr触点。发现哪些物理机制决定了切换操作的影响。