首页> 外文期刊>IEEE Transactions on Power Delivery >Radio and audible noise performance of T2 conductors
【24h】

Radio and audible noise performance of T2 conductors

机译:T2导体的无线电和听觉噪声性能

获取原文
获取原文并翻译 | 示例
           

摘要

The Central Iowa Power Cooperative (CIPCO) plans to build a 345 kV overhead power line using a bundle of four Partridge T2 conductors. The T2 conductor is two normal cylindrical conductors twisted together to prevent galloping during freezing rain and wind. Since it was not known whether any of the analytical expressions for calculating the radio and audible noise performance of conductors would work for T2 conductors, measurements were performed in the Bonneville Power Administration's (BPA) high voltage laboratory to compare the radio influence voltage (RIV) and audible noise (AN) performance of the Partridge T2, Partridge and Dove conductors. The Dove conductor has about the same cross-section and current-carrying capacity as the Partridge T2 conductor. The tests showed that no consistent, measurable difference could be found in the RIV and AN levels between the Partridge T2 and Dove conductors under dry or artificial rain conditions and whether the conductors were arranged in bundles of 4, 3, or 2 subconductors or as single conductors.
机译:爱荷华州中央电力合作社(CIPCO)计划使用四根Partridge T2导体束来构建345 kV架空电力线。 T2导体是两根普通的圆柱形导体,扭曲在一起,以防止在冻雨和刮风时舞动。由于尚不清楚用于计算导体的无线电和听觉噪声性能的任何分析表达式是否适用于T2导体,因此在Bonneville电力局(BPA)高压实验室进行了测量,以比较无线电影响电压(RIV)以及Partridge T2,Partridge和Dove导体的听觉噪声(AN)性能。鸽子导体的横截面和载流能力与Part T2导体大致相同。测试表明,在干燥或人工降雨条件下,Partridge T2和Dove导体之间的RIV和AN含量均未发现一致,可测量的差异,并且该导体是以4、3或2个子导体的束或单个排列的指挥。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号