首页> 外文期刊>IEEE Transactions on Power Delivery >Dielectric strength of transformer insulation at DC polarity reversal
【24h】

Dielectric strength of transformer insulation at DC polarity reversal

机译:直流极性反转时变压器绝缘的介电强度

获取原文
获取原文并翻译 | 示例
           

摘要

Among special insulation tests for DC power converter transformers, polarity reversal tests can be substituted by applied AC voltage tests from a stress similarity in oil ducts. In order to investigate equivalent levels of other insulation tests to polarity reversal tests, the dielectric strength of a transformer at polarity reversals was examined by use of a model of typical oil/paper composite insulation. From the comparison of polarity reversal and other insulation tests, it was found that dielectric strength of transformer insulation at polarity reversals is phenomenally similar to that under switching impulse stresses. Equivalent AC test voltage to polarity reversal test was also estimated from the experimental results. The breakdown characteristics of polarity reversal tests showed that partial discharges at polarity reversals impose less harmful stress on insulation barriers than those at usual AC or impulse tests.
机译:在直流电源换流变压器的特殊绝缘测试中,可以根据油管中的应力相似性,通过施加的交流电压测试来替代极性反转测试。为了研究其他绝缘测试与极性反转测试的等效水平,通过使用典型的油/纸复合绝缘模型来检查变压器在极性反转时的介电强度。通过极性反转和其他绝缘测试的比较,发现变压器绝缘在极性反转时的介电强度与开关脉冲应力下的介电强度惊人地相似。从实验结果还可以估算出与极性反转测试等效的交流测试电压。极性反转测试的击穿特性表明,与普通的交流或脉冲测试相比,极性反转的局部放电对绝缘屏障施加的有害应力较小。