首页> 外文期刊>IEEE Transactions on Power Delivery >Influence of single-phase excitation and magnetizing reactance on transformer leakage reactance measurement
【24h】

Influence of single-phase excitation and magnetizing reactance on transformer leakage reactance measurement

机译:单相励磁电抗对变压器漏电抗测量的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Low voltage and single-phase excitation are often used to measure leakage reactance or short-circuit impedance of transformers. Winding distortion may be detected by comparing field results with factory nameplate values measured at 25-100% of the rated current using three-phase excitation. The results of single- and three-phase excitation will not always correlate. If the voltage applied in the field is not properly selected then the data may be influenced by the magnetizing reactance. The resulting difference between the nameplate value and the field data might then lead to erroneous analysis of test results and could be interpreted as an indication of winding distortion. The intent of this paper is to analyze the physics of the process and gain insight on test circuit selection and analysis of the results. Methods for avoiding erroneous test results are suggested.
机译:低压和单相励磁通常用于测量变压器的泄漏电抗或短路阻抗。通过将现场结果与使用三相励磁在额定电流的25-100%处测得的出厂铭牌值进行比较,可以检测到绕组变形。单相和三相激励的结果并不总是相关的。如果未正确选择在磁场中施加的电压,则磁化电抗可能会影响数据。铭牌值与现场数据之间的差异可能会导致测试结果的错误分析,并可能被解释为绕组变形的指示。本文的目的是分析过程的物理过程,并获得对测试电路选择和结果分析的了解。建议避免错误测试结果的方法。