The energy absorption capability and time-to-failure of varistors used in station-class metal-oxide surge arresters

机译:站级金属氧化物避雷器中使用的压敏电阻的能量吸收能力和失效时间

获取原文
获取原文并翻译 | 示例
           

摘要

Varistors for use in station-class surge arresters were tested to destruction to determine their energy absorption capability at current levels ranging from 0.8 A/sub peak/ to 35 kA/sub peak/. Typical mean values increased from 400-600 J/cm/sup 3/ at the lower current end to 1600-2000 J/cm/sup 3/ at 35 kA/sub peak/. The product of the mean time-to-failure and the mean current was found to be a constant over five orders of magnitude. The varistor failure mode was found to be a characteristic of the current magnitude. It is recommended that standard test methods be developed for the energy absorption capability of metal-oxide surge arresters, and be included in relevant standards.
机译:对用于站级避雷器的压敏电阻进行了破坏测试,以确定它们在0.8 A / sub peak /至35 kA / sub peak /电流范围内的能量吸收能力。典型平均值从较低电流端的400-600 J / cm / sup 3 /增加到35 kA / sub peak /时的1600-2000 J / cm / sup 3 /。发现平均故障时间与平均电流的乘积在五个数量级上是恒定的。发现压敏电阻故障模式是电流幅度的特征。建议针对金属氧化物电涌放电器的能量吸收能力开发标准测试方法,并将其包括在相关标准中。