摘要

The effectiveness of lightning protection methods, such as lowering the grounding resistance and reducing the installation interval of surge arresters, for preventing damage to arresters on power distribution lines caused by direct lightning strokes in winter is investigated. Furthermore, several countermeasures for arrester outages which occur in spite of the installation of an overhead ground wire are studied quantitatively. The main results are as follows: (1) the installation of an additional overhead ground wire is more effective in preventing damage to arresters caused by winter lightning than increasing the withstand capability of arresters, by a factor of two; (2) and lowering the grounding resistance of arresters to 30 /spl Omega/ is not effective in reducing the number of arrester outages.
机译:研究了防雷方法的有效性,例如降低接地电阻和减小电涌放电器的安装间隔,以防止冬季直接雷击对配电线路的避雷器造成损坏。此外,定量研究了尽管安装了架空接地线但仍发生的避雷器停机的几种对策。主要结果如下:(1)安装额外的架空接地线比防止避雷器的承受能力提高两倍,更有效地防止了冬季雷电对避雷器的损坏; (2)将避雷器的接地电阻降低至30 / spl Omega /并不能有效减少避雷器的停机次数。