首页> 外文期刊>IEEE Transactions on Power Delivery >Maximum step voltages of combined grid-multiple rods ground electrodes
【24h】

Maximum step voltages of combined grid-multiple rods ground electrodes

机译:并网多棒接地电极的最大阶跃电压

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Expressions are suggested for assessing the maximum step-voltages and associated parameters of combined grid-multiple rods ground electrodes buried in uniform soil. The expressions proposed are successfully verified by comparison to exact computer calculations performed for a wide set of square and rectangular ground grids reinforced by ground rods distributed around the grid perimeter and within the grid.
机译:建议用表达式来评估埋在均匀土壤中的并网多棒接地电极的最大阶跃电压和相关参数。通过与对由分布在网格周边和网格内的接地棒加强的各种正方形和矩形接地网格进行的精确计算机计算进行比较,成功地验证了所提出的表达式。