首页> 外文期刊>IEEE Transactions on Power Delivery >Monitoring results of the effectiveness of surge arrester spacings on distribution line protection
【24h】

Monitoring results of the effectiveness of surge arrester spacings on distribution line protection

机译:避雷器间距对配电线路保护有效性的监控结果

获取原文
获取原文并翻译 | 示例
           

摘要

Surge arresters were evaluated as a means of improving reliability by reduction in 13 kV distribution line flashovers; five feeders were extensively monitored for three years. Lightning-caused faults were detected with the US National Lightning Detection Network, magnetic-field and optical sensors attached to fault recorders, and lightning-activated camera systems. Three circuits had arresters added on all phases with spacings of 40 m (every pole), 200 m, and 400 m respectively. Two other control circuits had no additional arresters. There was no discernible difference in the lightning performance of the circuits outfitted with the different arrester spacings when line length and lightning flash exposure are considered. Evidence indicated that most of the faults were caused by direct strokes rather than induced voltage flashovers. The monitored circuits are in areas with relatively heavy tree coverage which should reduce the number of direct strokes but cause higher induced voltages. In a surprising result, the circuit with arresters installed on every pole had several lightning-caused faults.
机译:通过减少13 kV配电线路闪络,评估了避雷器作为提高可靠性的一种手段。五年对五台进料器进行了广泛监控。通过美国国家闪电检测网络,连接到故障记录器的磁场和光学传感器以及闪电激活的摄像头系统,可以检测到由闪电引起的故障。三个回路在所有相上都添加了避雷器,每个避雷器的间距分别为40 m(每极),200 m和400 m。其他两个控制电路没有额外的避雷器。当考虑线长和雷电暴露时,配备有不同避雷器间距的电路的雷电性能没有明显差异。有证据表明,大多数故障是由直行程引起的,而不是由感应电压闪络引起的。受监视的电路位于树木覆盖较重的区域,这应减少直接击中次数,但会引起较高的感应电压。令人惊讶的结果是,在每个极上都安装了避雷器的电路出现了几个由雷电引起的故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号