首页> 外文期刊>IEEE Transactions on Power Delivery >A busbar protection technique and its performance during CTsaturation and CT ratio-mismatch
【24h】

A busbar protection technique and its performance during CTsaturation and CT ratio-mismatch

机译:电流互感器饱和和电流互感器比例不匹配时的母线保护技术及其性能

获取原文
获取原文并翻译 | 示例
           

摘要

This paper describes a digital technique for protecting busbars.nThe technique uses positive- and negative-sequence models of the powernsystem in a fault-detection algorithm. While phase voltages and currentsnare used to detect faults, parameters of the power system are not used.nAn analysis of the performance of the proposed technique during CTnsaturation and ratio-mismatch conditions is presented. The performancenof the technique was investigated for a variety of operating conditionsnand for several busbar configurations. Data generated by EMTPnsimulations of model power systems were used in the investigations. Thenresults indicate that the proposed technique is stable during CTnsaturation and ratio-mismatch conditions
机译:本文介绍了一种用于保护母线的数字技术。n该技术在故障检测算法中使用电力系统的正序和负序模型。虽然使用相电压和电流来检测故障,但并未使用电力系统的参数。n对所提出的技术在CT饱和和比率不匹配条件下的性能进行了分析。研究了该技术在各种运行条件下以及几种母线配置下的性能。在调查中使用了由模型电力系统的EMTPn仿真产生的数据。结果表明,所提出的技术在CT饱和和比例失配条件下是稳定的。