Melting and breaking characteristics of OPGW strands by lightning

机译:OPGW绞线的雷电熔化和断裂特性

获取原文
获取原文并翻译 | 示例
       

摘要

Some strands were melted and broken in a 140 mm2 OPGW (composite fiber-optic ground wire) in a 187 kV transmission line. It was assumed that this was caused by a lightning strike. DC arc tests simulating lightning strikes were carried out, and the melting and breaking characteristics of OPGW strands were obtained. The electric charge of the lightning strike that damaged the OPGW was estimated from the number of strands broken by the DC arc. In this paper, the DC arc test results, and the test conditions required to simulate a powerful lightning strike are described.
机译:在187 kV输电线路的140 mm2 OPGW(复合光纤接地线)中,一些线束熔化并断裂。假定这是由雷击引起的。进行了模拟雷击的直流电弧试验,获得了OPGW绞线的熔化和断裂特性。根据直流电弧折断的股数,估算了损坏OPGW的雷击电荷。本文介绍了直流电弧测试结果以及模拟强大雷击所需的测试条件。