首页> 外文期刊>IEEE Transactions on Power Delivery >Seismic behavior of flexible conductors connecting substation equipment-part II: shake table tests
【24h】

Seismic behavior of flexible conductors connecting substation equipment-part II: shake table tests

机译:连接变电站设备的柔性导体的抗震性能-第二部分:振动台试验

获取原文
获取原文并翻译 | 示例
           

摘要

Due to failures of interconnected equipment in recent earthquakes, it is suspected that the seismic interaction of the flexible conductors with the equipment during a strong ground motion could cause additional unpredicted forces, resulting in damage or collapse of the equipment they interconnect. This paper presents the results of an investigation into the dynamic behavior of flexible conductors by performing several shake table tests on a class of flexible conductors and the relevant 500-kV interconnected equipment used in substations throughout the province of British Columbia in Canada. The test specimen consisted of large scale models of the equipment items and the actual size flexible conductors. The shake table input records were synthetic earthquakes generated to fit an IEEE prescribed response spectrum. This investigation showed that the dynamic effect of flexible conductors must be considered when evaluating the seismic capacity of interconnected equipment.
机译:由于最近地震中互连设备的故障,怀疑在强地面运动期间柔性导体与设备之间的地震相互作用可能会导致额外的不可预知的力,从而导致互连设备损坏或崩溃。本文通过对加拿大不列颠哥伦比亚省的变电站中使用的一类柔性导体和相关的500 kV互连设备进行几次振动台测试,提出了对柔性导体的动态行为进行调查的结果。测试样本由设备项目的大型模型和实际尺寸的柔性导体组成。摇表输入记录是为适应IEEE规定的响应谱而生成的合成地震。这项研究表明,在评估互连设备的抗震能力时,必须考虑柔性导体的动态影响。