首页> 外文期刊>IEEE Transactions on Power Delivery >Safety assessment of bulk and traction supply substations in Taipei rail transit systems
【24h】

Safety assessment of bulk and traction supply substations in Taipei rail transit systems

机译:台北轨道交通系统散装和牵引供电变电站的安全评估

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a practical case for safety assessment of bulk supply substations (BSS) and traction supply substations (TSS) in Taipei Rail Transit Systems (TRTS). For a substation grounding system to be safe, the maximum touch-and-step voltages should not exceed postulated safety criteria. The safety criterion in IEEE Standard 80 is defined in terms of permissible body current. The permissible body current is then translated into the permissible touch-and-step voltages. Since the mesh voltage is usually the worst possible touch voltage inside the substation (excluding transferred potentials), the mesh voltage is used as the safety criteria. In other words, safety assessment of an ac substation grounding system in TRTS is referred to a procedure by which the mesh and step voltages are computed and compared to the maximum permissible (safe) touch-and-step voltages. Computation results for the orange line at O19 station are presented.
机译:本文为台北轨道交通系统(TRTS)中的大宗供应变电站(BSS)和牵引供应变电站(TSS)的安全评估提供了一个实际案例。为了使变电站接地系统安全,最大步进电压不得超过假定的安全标准。 IEEE标准80中的安全标准是根据允许的体电流定义的。然后将允许的人体电流转换为允许的触碰电压。由于网状电压通常是变电站内部可能的最坏接触电压(不包括转移的电势),因此将网状电压用作安全标准。换句话说,TRTS中交流变电站接地系统的安全评估是指计算网格电压和阶跃电压并将其与最大允许(安全)接触阶跃电压进行比较的过程。给出了O19站橙色线的计算结果。