首页> 外文期刊>IEEE Transactions on Power Delivery >The ultra-saturation phenomenon of loaded transformer energization and its impacts on differential protection
【24h】

The ultra-saturation phenomenon of loaded transformer energization and its impacts on differential protection

机译:负载变压器通电的超饱和现象及其对差动保护的影响

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

A sort of unusual maloperation of the differential protection of the transformer and delayed maloperations due to the loaded transformer energization are reported. A second-order equivalent circuit-based model is set up to investigate this phenomenon. With rational assumptions and simplifications, the analytical solution of the main flux of the transformer is obtained. On the basis of the expression of the flux, the delayed maloperation can be explained in a rational way. Furthermore, a peculiar transient phenomenon of transformer energization, specified as "ultra-saturation" in this paper, is revealed. It was substantiated to be a more severely adverse condition in terms of the security of the transformer differential protection. In the extreme case, all existing blocking schemes implemented with the identification of the characteristics of inrushes or fluxes will be of no effect regardless of how to set the threshold. A variety of the simulation tests proves that the delayed maloperation of the differential protection and ultra-saturation of the transformer core may occur in the occasion of loaded transformer energization.
机译:据报道,一种变压器差动保护的异常动作是由于负载变压器通电而引起的误动作。建立了基于二阶等效电路的模型来研究此现象。通过合理的假设和简化,得出了变压器主磁通的解析解。根据流量的表达,可以合理地解释延迟误动。此外,揭示了一种特殊的变压器通电瞬态现象,在本文中称为“超饱和”。就变压器差动保护的安全性而言,它被证明是更为严重的不利条件。在极端情况下,无论如何设置阈值,所有用于识别涌流或通量特性的现有阻塞方案都将无效。各种模拟测试证明,在变压器带电负载的情况下,差动保护的延迟误动作和变压器铁芯的超饱和可能会发生。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号