首页> 外文期刊>IEEE Transactions on Power Delivery >Analysis of zig-zag transformer applying in the three-phase four-wire distribution power system
【24h】

Analysis of zig-zag transformer applying in the three-phase four-wire distribution power system

机译:之字形变压器在三相四线配电系统中的应用分析

获取原文
获取原文并翻译 | 示例
       

摘要

The load unbalance and the nonlinear loads result in a significant neutral current in the three-phase four-wire distribution power system. The Zig-Zag transformer has been proposed to attenuate the neutral current of the three-phase four-wire distribution power system. In this paper, an analysis is carried out and computer simulation is used to evaluate the performance of the Zig-Zag transformer under ideal and nonideal power conditions. The simulation results show that (a) the Zig-Zag transformer can effectively attenuate the neutral current and zero-sequence harmonic currents on the utility side under the balanced utility voltage, (b) the utility side neutral current becomes larger under the unbalanced utility voltage or the distorted utility voltage with zero sequence harmonic components after applying the Zig-Zag transformer, (c) the insertion of an inductor in the utility side of the neutral conductor can alleviate overloading of the neutral current caused by the unbalanced utility voltages and the distorted utility voltages with zero sequence harmonic components.
机译:负载不平衡和非线性负载会在三相四线配电电源系统中产生很大的中性线电流。已经提出使用之字形变压器来衰减三相四线配电电力系统的中性电流。本文进行了分析,并使用计算机仿真来评估Zig-Zag变压器在理想和非理想功率条件下的性能。仿真结果表明:(a)Zig-Zag变压器可以在平衡的市电电压下有效衰减市电侧的中性线电流和零序谐波电流;(b)在不平衡的市电电压下,市电侧中性线电流会变大或在应用Zig-Zag变压器后失真的具有零序谐波分量的市电电压,(c)在中性导体的市电侧插入电感器可以减轻由不平衡的市电电压和失真引起的中性电流过载。具有零序谐波分量的市电电压。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号