A method of symmetrical component analysis for the detection of current-transformer (CT) saturation in a numerical current differential feeder protection relay is presented in this paper. The performance of the differential relay is investigated for various faults on a typical Electro-Magnetic Transients Program/Alternative Transients Program (EMTP/ATP) simulated transmission feeder. The simulator includes the effects of CT saturation. A comparison between simulation and tests conducted on an analog model testbench are also evaluated. The results show a high degree of similarity and illustrate the effect that CT saturation imposes on the sensitivity and stability of the protection scheme. An algorithm is presented that shows significant improvement in sensitivity on internal faults while still maintaining a high level of stability on external faults and nonfault events.
机译:提出了一种用于数字电流差动馈线保护继电器中电流互感器饱和检测的对称分量分析方法。在典型的电磁暂态程序/交流暂态程序(EMTP / ATP)模拟传输馈线中,针对各种故障研究了差动继电器的性能。该模拟器包括CT饱和度的影响。还评估了模拟与在模拟模型测试平台上进行的测试之间的比较。结果显示出高度的相似性,并说明了CT饱和度对保护方案的敏感性和稳定性的影响。提出了一种算法,该算法显示出对内部故障的敏感性有了显着提高,同时仍保持了对外部故障和非故障事件的高度稳定性。