Anti-islanding protection of distributed generators (DG) is a significant technical barrier to the emerging DG industry. This paper presents an innovative power line signaling based anti-islanding scheme developed in response to the challenge. The scheme broadcasts a signal from a substation to the DG sites using the distribution feeders as the signal paths. A DG is considered as islanded from the upstream system if the signal cannot be detected at the DG site. The proposed scheme has been evaluated using analytical, simulation and field tests. The results are very promising. This paper presents the main ideas of the scheme and its design considerations. Methods to create and detect the signals are shown and their performances are analyzed.
机译:分布式发电机(DG)的防孤岛保护是新兴DG行业的重要技术障碍。本文提出了一种创新的基于电力线信号的抗孤岛方案,以应对这一挑战。该方案使用分配馈线作为信号路径,将信号从变电站广播到DG站点。如果无法在DG站点检测到信号,则认为DG是上游系统的孤岛。拟议的方案已通过分析,模拟和现场测试进行了评估。结果是非常有希望的。本文介绍了该方案的主要思想及其设计注意事项。展示了创建和检测信号的方法,并分析了它们的性能。