首页> 外文期刊>IEEE Transactions on Power Delivery >Influence of VFT on Shell-Type Transformer
【24h】

Influence of VFT on Shell-Type Transformer

机译:VFT对壳式变压器的影响

获取原文
获取原文并翻译 | 示例
           

摘要

When a disconnecting switch in a gas insulated switchgear (GIS) operates, a high frequency oscillating surge called very fast transient (VFT) is generated. The VFT may set off overvoltage in a transformer winding. In the paper the authors evaluate the influence of VFT on a shell-type transformer. To simulate waveforms of VFT invading a transformer, a simple equivalent circuit for a shell-type transformer in a high frequency range is derived experimentally. Using this model the overvoltage waveforms are analyzed for various configurations of GIS. Then, the influence of VFT on a 500 kV shell-type transformer winding is investigated. The results lead to a conclusion that VFT does not threaten the reliability of insulation of the transformer winding
机译:当气体绝缘开关设备(GIS)中的隔离开关工作时,会产生称为非常快速瞬态(VFT)的高频振荡浪涌。 VFT可能会引起变压器绕组中的过电压。在本文中,作者评估了VFT对壳式变压器的影响。为了模拟入侵变压器的VFT波形,实验得出了一个壳式变压器在高频范围内的简单等效电路。使用该模型,可以分析GIS各种配置的过电压波形。然后,研究了VFT对500 kV壳式变压器绕组的影响。结果得出结论,VFT不会威胁变压器绕组绝缘的可靠性