Locating and Isolating DC Faults in Multi-Terminal DC Systems

机译:在多端子直流系统中定位和隔离直流故障

获取原文
获取原文并翻译 | 示例

摘要

A VSC-MTDC (multi-terminal dc) system consists of Voltage-Source Converters (VSCs) connected to a dc network at their dc terminals. The MTDC is most vulnerable to a dc fault which paralyses all the VSCs until the dc fault is cleared. As dc circuit breakers are expensive, this paper proposes a solution based on extinguishing the dc fault current by opening all the ac-circuit breakers (ac-CBs) which the VSCs are already equipped with on the ac-sides. However, it is necessary to identify which dc line is the faulted line (in case it is a permanent fault) so that it can be isolated by fast dc switches (which are much more economical than the dc circuit breakers), prior to restoring the MTDC system by re-closing all the ac-CBs. This paper presents the handshaking method, which locates and isolates the faulted dc line and restores the MTDC without telecommunication.
机译:VSC-MTDC(多端子直流)系统由电压源转换器(VSC)组成,这些电压源转换器的直流端子连接到直流网络。 MTDC最容易遭受直流故障,该故障会使所有VSC瘫痪,直到清除直流故障为止。由于直流断路器价格昂贵,因此本文提出了一种解决方案,即通过断开VSC在交流侧已经配备的所有交流断路器(ac-CB)来消除直流故障电流。但是,必须先确定哪条直流线是故障线(如果是永久性故障),以便可以在恢复直流电之前通过快速的直流开关(比直流断路器经济得多)将其隔离。通过重新关闭所有交流CB的MTDC系统。本文提出了一种握手方法,该方法可以定位和隔离有故障的直流线路,并在无需电信的情况下恢复MTDC。