首页> 外文期刊>IEEE Transactions on Power Delivery >Study of Corona Discharge Pattern on High Voltage Transmission Lines for Inspecting Faulty Porcelain Insulators
【24h】

Study of Corona Discharge Pattern on High Voltage Transmission Lines for Inspecting Faulty Porcelain Insulators

机译:瓷绝缘子故障高压输电线路电晕放电方式的研究

获取原文
获取原文并翻译 | 示例
           

摘要

The corona pattern from porcelain insulator strings on high voltage (HV) transmission lines has been investigated for inspecting faulty insulators on-line. Corona patterns from HV conductive line, metal accessory, and discharge patterns from bad connection, power stations, have also been studied for background pulse noise elimination. A pattern recognition method for inspecting faulty porcelain insulators is proposed, which consists of several criteria. It is found that the harmonics and carriers from the transmission lines influence the recognition seriously, which can be eliminated by choosing a high frequency band of sensors (2 MHz–20 MHz). Based on the above investigations, an instrument was developed and used on the field measurements in Lanzhou and Zhengzhou power utilities in China. The field results show a strong support for this method. On the measurement of 76 towers, the measuring accuracy of inspecting faulty insulators was about 87.5%.
机译:已经研究了高压(HV)传输线上的瓷绝缘子串的电晕图案,用于在线检查有故障的绝缘子。还研究了高压导线,金属附件的电晕图案和发电厂连接不良的放电图案,以消除背景脉冲噪声。提出了一种检查瓷绝缘子故障的模式识别方法,该方法包括多个标准。发现来自传输线的谐波和载波会严重影响识别,可以通过选择传感器的高频带(2 MHz–20 MHz)来消除。基于以上研究,开发了一种仪器,用于中国兰州和郑州电力公司的现场测量。现场结果显示了对该方法的有力支持。在测量76座塔时,检查故障绝缘子的测量精度约为87.5%。