The flashover rate of a distribution line associated with indirect lightning flashes is investigated based on numerical calculations and statistical analysis by taking account of the correlation between the peak value and the front duration of negative return-stroke current waveforms. When the grounding interval of an overhead ground wire and/or surge arresters is 200 m, surge arresters are more effective than an overhead ground wire in suppressing flashover of the power lines, and installation of both is very effective. The flashover rate decreases if there is correlation between the peak and the front duration of lightning current; and it significantly decreases with the increase of the ground conductivity. When the line is equipped with surge arresters only, the flashover rate associated with subsequent strokes is higher than that associated with first strokes; and calculation with the fixed front duration of 2 $mu$ s for first stroke current does not always result in good estimates of flashover rate.
机译:考虑到负向冲程电流波形的峰值与前沿持续时间之间的相关性,基于数值计算和统计分析,研究了与间接雷电相关的配电线路的闪络率。当架空接地线和/或电涌放电器的接地间隔为200 m时,在抑制电源线的飞弧方面,电涌放电器比架空接地线更有效,并且两者的安装都非常有效。如果峰值和雷电流的持续时间之间存在相关性,则闪络率会降低;并且随着地面电导率的增加而显着降低。当生产线仅配备电涌放电器时,与后续行程相关的闪络率高于与第一行程相关的闪络率。而且,对于第一冲程电流,使用固定的前端持续时间2μμs进行计算,并不总是能很好地估计闪络率。