首页> 外文期刊>Power Delivery, IEEE Transactions on >The FRTU-Based Fault-Zone Isolation Method in the Distribution Systems
【24h】

The FRTU-Based Fault-Zone Isolation Method in the Distribution Systems

机译:配电系统中基于FRTU的故障区域隔离方法

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper, an intelligent feeder remote terminal unit (FRTU)-based operation and control strategy is proposed, which can improve the accuracy and quickness of the fault-zone determination and isolation from such problems as general fault, high impedance fault (HIF) and in-rush current (IRC) in the distribution system, including overhead and underground feeders. In the proposed method, each FRTU inferring the fault or inrush current determines whether its feeder is a fault or not, and whether its sink zone is a fault zone or not, by exchanging fault information (such as current value, voltage value, current direction) with the other FRTUs on the feeders under the ubiquitous-based distribution system that enables the FRTUs to be connected freely to the network. In order to explain the effectiveness of the proposed method, several cases are simulated for typical distribution using the developed simulator.
机译:本文提出了一种基于智能馈线远程终端单元(FRTU)的操作和控制策略,可以提高故障区域确定和隔离一般故障,高阻抗故障(HIF)等问题的准确性和敏捷性。配电系统中的浪涌电流(IRC),包括架空和地下馈线。在提出的方法中,每个FRTU推断故障或浪涌电流,通过交换故障信息(例如电流值,电压值,电流方向)来确定其馈线是否为故障,以及其下陷区是否为故障区。 )以及基于无处不在的分发系统下的馈线上的其他FRTU,这使得FRTU可以自由连接到网络。为了说明所提出方法的有效性,使用开发的模拟器对几种情况进行了典型分布的模拟。