首页> 外文期刊>Power Delivery, IEEE Transactions on >Eigenvalue Analysis for Investigation of Tilting of Transformer Winding Conductors Under Axial Short-Circuit Forces
【24h】

Eigenvalue Analysis for Investigation of Tilting of Transformer Winding Conductors Under Axial Short-Circuit Forces

机译:特征值分析在轴向短路力作用下变压器绕组导体倾斜的研究

获取原文
获取原文并翻译 | 示例
           

摘要

The tilting phenomenon may lead to a catastrophic failure, such as an interturn fault in transformers, under the action of axial short-circuit electromagnetic forces. In this paper, first, a state-space approach has been used to determine the eigenvalues of various winding configurations used in practice by assuming a small value of tilt angle up to 10°. These eigenvalues decide the critical tilting forces and the natural frequencies of windings. The four cases involving disk, layer, helical windings (all these with strip conductor), and layer winding with continuously transposed cable conductor have been analyzed. Further, initial critical tilt angles are determined for various magnitudes of the axial force in a typical 5-MVA transformer.
机译:在轴向短路电磁力的作用下,倾斜现象可能导致灾难性故障,例如变压器的匝间故障。在本文中,首先,采用状态空间方法来确定实际中使用的各种绕组配置的特征值,方法是假设倾斜角的值小到10°。这些特征值决定了临界的倾斜力和绕组的固有频率。分析了盘,层,螺旋绕组(均带有条形导体)和具有连续换位电缆导体的层绕组这四种情况。此外,在典型的5-MVA变压器中,针对轴向力的各种大小确定了初始临界倾斜角。