首页> 外文期刊>Power Delivery, IEEE Transactions on >Power Transformer Differential Protection Based on Clarke's Transform and Fuzzy Systems
【24h】

Power Transformer Differential Protection Based on Clarke's Transform and Fuzzy Systems

机译:基于克拉克变换和模糊系统的电力变压器差动保护

获取原文
获取原文并翻译 | 示例
           

摘要

The power transformer is a piece of electrical equipment that needs continuous monitoring and fast protection since it is very expensive and an essential element for a power system to perform effectively. The most common protection technique used is the percentage differential logic, which provides discrimination between an internal fault and different operating conditions. Unfortunately, there are some operating conditions of power transformers that can affect the protection behavior and the power system stability. This paper proposes the development of a new algorithm to improve the differential protection performance by using fuzzy logic and Clarke's transform. An electrical power system was modeled using Alternative Transients Program (ATP) software to obtain the operational conditions and fault situations needed to test the algorithm developed. The results were compared to a commercial relay for validation, showing the advantages of the new method.
机译:电力变压器是一种需要持续监控和快速保护的电气设备,因为它非常昂贵,并且是电力系统有效运行的基本要素。最常用的保护技术是百分比差分逻辑,该逻辑可区分内部故障和不同的工作条件。不幸的是,电力变压器的某些工作条件会影响保护行为和电力系统的稳定性。本文提出了一种利用模糊逻辑和克拉克变换提高差动保护性能的新算法。使用替代暂态程序(ATP)软件对电力系统进行建模,以获得测试开发的算法所需的运行条件和故障情况。将结果与商用继电器进行比较以进行验证,显示了新方法的优势。