Disconnector switching operations in large gas-insulated switchgear (GIS) systems may produce very fast transient overvoltages (VFTOs), causing high electric stress to other apparatuses in the substation, such as power transformers. This paper presents a VFTO measuring technique based on a transformer bushing sensor, which consists of the transformer bushing (C1) and a capacitor sensor (C2) installed at the test tap of transformer bushing. In order to solve the problem of the frequency limitation of the transformer bushing sensor for measuring VFTO, a convolution model on the square-wave response of the transformer bushing sensor is introduced to obtain the frequency response of the transformer bushing sensor, and a deconvolution model based on the incremental Wiener filter is applied to reconstruct the input transient voltage waveform at the tip of the bushing by using the output signals from the bushing sensor. A 110-kV transformer bushing sensor and a fast transient overvoltage source are built in our laboratory. The results from the laboratory indicate that a transient voltage can be measured correctly based on our technique with the 110-kV transformer bushing sensor. A 750-kV transformer bushing sensor is built in a 750-kV substation. The measuring results from the 750-kV substation by using our technique show that the peak value of the VFTO produced by the disconnector (AIS) switching off operations is about 775 kV, and the dominant oscillating frequencies of the VFTO are 3.5 MHz, 1.6 MHz, and 650 kHz.
机译:大型气体绝缘开关设备(GIS)系统中的隔离开关操作可能会产生非常快速的瞬态过电压(VFTO),从而对变电站中的其他设备(例如电力变压器)造成高电应力。本文提出了一种基于变压器套管传感器的VFTO测量技术,该技术由安装在变压器套管测试抽头处的变压器套管(C1)和电容器传感器(C2)组成。为了解决测量VFTO的变压器套管传感器的频率限制问题,引入了关于变压器套管传感器方波响应的卷积模型,以获得了变压器套管传感器的频率响应,并进行了反卷积模型基于增量式维纳滤波器的滤波器,通过使用套管传感器的输出信号,可重构套管尖端的输入瞬态电压波形。我们的实验室内置了一个110 kV变压器套管传感器和一个快速瞬态过电压源。实验室的结果表明,根据我们的技术,使用110 kV变压器套管传感器可以正确测量瞬态电压。 750 kV变电站中内置有750 kV变压器套管传感器。使用我们的技术对750 kV变电站进行的测量结果表明,隔离开关(AIS)断开操作产生的VFTO的峰值约为775 kV,并且VFTO的主振荡频率为3.5 MHz,1.6 MHz和650 kHz。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号